Warning: This is an "include" page. As such, its contents may be included in multiple other pages. To see a list of all pages that include this page, click on "What links here" in the bottom left navbar. If you make changes to this page, be sure that your changes are appropriate to all pages on which this content will be included. You are also encouraged to review our Zaber Wiki Editing Guidelines. This header will not be included in other pages.

Instruction Name Set Knob Direction
Applies to A-Series motorized devices
Firmware Version 6.xx
Command Number 108
Command Type Setting
Command Data Knob Direction
Reply Data Knob Direction
Safe to retry? Yes
Returns Current Position? No
Persistence Non-Volatile
Summary Changes direction of movement when knob is turned.

Use this command to reverse the device movement direction when the knob is turned.

0 - Normal (Default)
Clockwise knob turn results in movement in the positive direction.
1 - Reversed
Clockwise knob turn results in movement in the negative direction.

This setting is identical to bit 9 of Set Device Mode (Cmd 40). Changes to either this setting or the device mode will be reflected in the other.

This setting is stored in non-volatile memory and will persist after power-down or reset.